gaz dedektörü
for continuous monitoring and warning of explosive gases and vapors. Suitable for use in heating and basement rooms, storage, office and residential premises. Not suitable for direct installation in hazardous areas. Warning device in a wall-mounted housing with acoustic and visual alarm message. Additional external signal devices, such as event detection system EMS, horns or warning lights, can be switched via the floating relay contact. Attention: Mounting material, assembly, wiring and connection are provided and carried out on site
Function:
continuous monitoring and warning of explosive gases
Application:
mainly in the home (building services), building technology and public facilities
Placement:
Wait, entrance, hallway/hallway, stairwell, electrical cabinet, etc.
Power supply:
230V/50Hz, 7VA recording power
Inputs:
2 gas sensors, depending on the choice, via cable NYM 3 (4) x 1.5 mm²
Alarm Threshold:
at approx. 20% LH
Show:
LEDs for operation, fault, alarm
Alarm output:
optically with LED (also on the sensor), acoustic with internal buzzer (approx. 80dB, 1m)
Outputs:
1 output relay/changeover (fail-safe principle) for additional external signal devices (horns, lights, etc.)
Switching capacity:
250V/50 Hz, 1A, resistive load
Temperature range:
+20°C to +40°C
Degree of protection:
IP 30
Design:
Wall-mounted enclosure, H x W x D = 188 x 100 x 65 mm
Option: Accessories such as panel mounting frame, gasket set or DIN rail clip